Programming 9651
Page 30 11772232
In addition to the three standard operating modes, there is a special Duress
mode which provides the same access as user mode but also secretly
communicates the duress status. There is only one user code of this type.
See Command 49 for details on how to enable Duress Code, and Commands
151-158 for details on how control the plug-by communicator outputs.
Entering Installer Mode
Chapter 3 describes how to enter installer mode for the first time in a new
installation. You can use this mode at any time, provided that the system is
unset and not in alarm. To enter installer mode:
1. Make sure the system is unset.
Note: If you have selected defaults for Finland, Norway, Sweden or Denmark
(Command 0), or a user has selected user command 3, you must enter a
valid user code at this point.
2. Press 0, then key in the Engineer Code (default 7890).
The display shows:
Installer Mode
You are now in installer mode.
While the system is in installer mode, all keypads except the one that you are
using will be locked and will display "Busy".
Using Programming and Testing Commands
When delivered from the factory, the control unit already has default settings.
To change the default settings:
1. Enter installer mode.
2. Key in the appropriate command number and press y.
The display shows the current value of the command.
3. Key in digits to select the value you require.
The display shows the new value.
4. Press y to store the new value of the command.
Note: If at any time you change your mind, repeat steps 1 to 3. The 9651
Quick Reference Programming Guide shows the commands and their
values. "Y" to the right of a value shows that it is the factory default.