Programming - Testing Commands 9651
Page 72 11772232
199: Display Zone Circuit Resistance
This command lets you view the resistance of zones connected to the control
unit. Either key in the zone number (single digit 1 to 8 only) or press C to step
up and A to step down through the zones. The bottom line of the display
shows the word “Panel” followed by the zone type, and then the resistance of
the zone in kilo Ohms. If the display shows “O/C” then the zone is open
circuit. “0k0” means that the zone is short-circuit.
991: Show Software Version
Use this command to show the software version installed within the control
unit.
1. Enter installer mode and key in 991 Y.
The display shows, for example:
9651 v4.03.0150
2. Press X to return to Installer Mode.