Cooper Security 9651 Installation Manual Page 54

  • Download
  • Add to my manuals
  • Print
  • Page
    / 88
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 53
Programming - Programming Commands 9651
Page 50 11772232
60: Level B Final Exit Operation
In a single system, this command specifies how the system treats Final Exit
zones during part set B. If you select option 0 (the default), Final Exit zones
included in Level B continue to act as Final Exit zones during part set B. If you
select option 1, these zones act as Normal Alarm zones during part set B.
61: Level B Entry Route Operation
In a single system, this command specifies how the system treats Entry Route
zones during part set B. If you select option 0 (the default), Entry Route zones
included in Level B continue to act as Entry Routes during part set B. If you
select option 1, these zones act as Final Exit zones during part set B.
62: Level B Exit Mode
This command sets the exit mode for Level B. The keypads give a double
"beep" confirmation tone at the end of all setting modes, including Silent Set.
The default is option 0, Timed.
Option
0 Timed. The keypad sounders and any internal sounders give a low
tone during exit of Level B. Use Command 65 to select the exit time.
1 Instant Set (no exit tone). Use this option to make the system set
without delay or exit tone.
2 Silent Set. Use this option to make the system set without an exit
tone. Use Command 65 to program the exit time.
3 Makes the Level B exit mode the same as Level A.
63: Level B Alarm Response
This command sets the alarm response for Level B.
Option
0 Keypad sounders only.
1 Internal sounders and keypad sounders (default).
2 Local alarm (internal and external sounder only).
3 Full alarm (communication and internal/external sounders).
Page view 53
1 2 ... 49 50 51 52 53 54 55 56 57 58 59 ... 87 88

Comments to this Manuals

No comments