7510r Appendix A
Page 79
BS 8473: 2006
In addition, if you wish the installation to comply with BS
8473 : 2006 then use the following commands:
Command Name Value Notes
System Options,
User Access
Reset After
Alarm
N Engineer Reset.
System Options,
Alarm Confirmation
Reset
Unconf/Conf
User/Installer Allows users to reset the
system after an unconfirmed
alarm, but not after a
confirmed alarm.
Alarm Filtering
The alarm system should either:
a) Have the means to indicate to the Alarm Receiving
Centre (ARC) whether the alarm system is set or unset
(open and close signals).
or
b) Be capable of generating a secondary signal
identifiable at the ARC as a mis-operation signal (Alarm
Abort).
To generate open, close, alarm confirm and alarm abort
signals in SIA or CID select
Reporting
,
Alarms
,
SIA Report
Mode, Summary (see page 57).
To generate those signals in Fast Format you must
reassign the alarm confirmation and zone omitted events
to two of the eight available channels (see page 56).