Engineer Menu 2-5 Engineering Manual
118
2 – Alternate
This is similar to the Consecutive option, but the panel attempts to connect to each ARC
only once before attempting the next. Once the last number has been attempted, the
system returns to the first and the sequence continues.
3 – All
With this option selected, the panel sends the alarm to all defined ARCs. The panel will
continue to attempt a connection to each ARC until the alarm has been sent to all of them.
Each telephone number is attempted a maximum of 15 times.
)
This option is applicable only if Fast Format is used (page 110). If SIA or Contact ID
is used, selecting All results in the same operation as the Alternate option.
Option 2 - 5 - 2 - 5: Configuring Restores
DigiCom-1 5
Restores
Restores 2
Enable
Restores 1
Disable
[
[
|
To enable/disable restore s
· Press| or ¬ to scroll, or
· Press the hot key
Press[ to save changes and continue
e.g.
1. SELECT RESTORES
You can use this option to specify whether or not to send "restore" messages to the ARC:
1 – Restore Signals Enabled
If you enable restores, the control unit sends both alarm and restore signals to the ARC.
For example, for a normal zone alarm, a restore message would indicate that the alarm has
been reset (this is not the same event as silencing the external sounders).
2 – Restore Signals Disabled
If you disable restores, the control unit will send alarm messages to the ARC, but will not
send restore messages.