Chapter 2: Getting Started
Starting the Panel for the First Time
Use the following procedure when starting a new system:
1. Follow the power-up procedure documented in the
Installation Instructions
. Make sure you apply a factory
restart to ensure that the system begins with its
factory default settings loaded.
The screen shows a start-up message similar to the
one at the right (text may vary depending on keypad):
SW VERSION
1.09 Jan 26 2007
2. If the panel's lid is off, the sounder may start soon
after power is switched on. This indicates a tamper
alarm.
3. You may see following message:
! Alerts !
00:00 19 Mon 01 JAN
4. Enter your engineer code (default 1234).
The screen shows:
At this point you can select one of two sets of defaults:
either PD6662 Grade 2, or PD6662 Grade 3. See page
133 for a listing of the default values. (If necessary, use
option 2-7-3-8 to change defaults at a later
date, see page 132.)
Country
UK PD6662 Grade 2
5. Press | or ¬ to select the defaults followed by [.
(Alternatively, press either 1 for Grade 2, or 2 for Grade
3.)
Note: If you select Grade 3 when starting the control unit
for the first time (or when returning a control unit to
its factory defaults) then the Engineer’s default code is
123400. If you select Grade 2 the default code is 1234.
The screen shows:
Language
English
6. Press | or ¬ to select the language used on the
keypad display, followed by [. (Note that the
software version may allow only one language.) The
screen shows:
[ENT] to CONFIRM
000 LECS
The next messages show the number of each type of
device found. EXP KEYPADS are keypads on an