Engineering Manual Engineer Menu 1-3
37
09 – Re-arms
If you select this attribute, the ward can rearm zones that have been triggered, but which
are now no longer in the alarm state at the end of the Bell Duration time (page 61). The
number of times the zone can rearm is specified by the No. of Rearms timer (page 65).
)
This attribute applies only if Confirmation Off is selected (page 89).
10 – Secure Ward
A Secure ward attempts to stay in a set condition. If the ward is unset, a "Hi Security Zone
Is Unset" alert message is displayed and the Hi Security timer starts (page 66). The timer
restarts each time a detector is triggered in the Secure ward. When the timer expires, the
system attempts to set the ward automatically.
11 – Bell & Strobe
This option allows you to select which wards will trigger the external sounder (bell) and
strobe outputs on the control panel. Refer to the Bell Delay and Bell Duration notes on
page 61.
12 – Foyer Mode
This enables ward 1 to:
Set automatically when all wards selected in the Foyer Mode attribute have been set. For
example if wards 2, 3 and 4 are selected, the system will automatically set ward 1
when the last of these wards is set.
Unset automatically when any one of the selected wards has been unset (with all the
wards being previously set).
Ward 1 is intended to be a foyer area, which needs to set or unset automatically.
)
To prevent the foyer setting before that of the last ward selected for setting, you
should ensure that the exit time of ward 1 (page 60) is greater than that of the
other wards.
)
Do not select ward 1 in the Foyer Mode option.
)
Ward 1 can be configured to set instantly; see page 88.
13 – Unset Fire
This attribute determines whether outputs that follow a Fire Alarm event (page 44 or 54)
activate only when a Fire zone (page 23) is set, or when the zone is either set or unset.
If a ward has this attribute, a fire alarm from the ward will activate the outputs if the ward
is set or unset. If a ward does not have this attribute, a fire alarm from the ward will
activate the outputs only when the ward is set.
14 – Multiply Ack
This option allows you to designate which wards will use the Double Knock counter (page
65).