Engineer Menu 1-5 Engineering Manual
66
26 – Payment Time
Not available in software version 3.11.07
27 – Hi Security
This timer determines the length of time that a secure ward (page 37) can remain unset
before the system automatically attempts to set it. When a secure ward is unset, activation
of any zone in that ward resets the timer.
28 – Supervision Warning
When set to 000 this timer disables all supervision warnings. When set to a positive
number between 001 and 999 this timer specifies the period in minutes that the control
unit waits after receiving a supervision signal from a transmitter. The control unit re-starts
the timer every time it receives a supervision signal from a transmitter. If the timer expires
before the next supervision signal is received then the control unit starts a supervision
warning and logs the event. The user can override the warning when setting the system.
The default setting for this timer is 16 minutes.
29 – Supervision Fail
When set to 000 this timer disables all supervision failures. When set to a positive number
between 001 and 999 the timer specifies in minutes the period that the control unit waits
after receiving a supervision signal from a detector. The control unit re-starts the timer
every time it receives a supervision signal from a transmitter. If the timer expires before
the next supervision signal is received then the control unit starts a supervision failure,
logs the event, and generates an alert.
The default value is 120 minutes (suitable for EN50131 systems).
On an EN50131 compliant system the detectors should transmit every four minutes.
30 – Set Status
This timer works in when Option 1 - 9 - 3 -20 is set to Timed (see page 95). When
set to 000 this timer stops the keypad showing the set/unset status after a the control unit
has completed setting a ward. When set to a positive number (and Option 1 - 9 - 3-
20 is set to Timed) then the keypad displays the set/unset status for the number of
seconds you select. If you set Option 1 - 9 - 3 -20 to Never or Always then this
time has no effect.
31 – Defer Count
This option specifies the maximum number of times that a user can defer an auto-set. You
can specify any number in the range 000 to 999. See page 70 for a description of setting
up auto-set timers.
32 – A.Set Warning
This option specifies the Auto-Set Warning time in minutes. You can enter any number
between 1 and 255. Use this option in conjunction with the Defer Setting timer, see page
64.