Engineer Menu 1-4 Engineering Manual
56
27 – Exit Flt
Activates when a zone in the selected ward is in a fault condition during the setting
procedure (e.g. a zone that does not have the Access attribute is activated); deactivates
when the fault is no longer present.
28 – Sndr Ctl.
Activates when a sound is required at a keypad assigned to the selected ward. For
example, for the Entry Delay or Exit timer (page 60) or an alarm condition.
By default, if a keypad is connected to an MSNode or MSPSU, it produces sounds for any
ward assigned to the Node (page 34). Keypads connected directly to the network produce
sounds for any ward assigned to the panel's extension loudspeaker (page 35). This output
type is used to ensure that a keypad produces sounds only for the ward selected for the
output.
To use this feature, assign the Sndr Ctl output type to the output of the relevant keypad
and fit the jumper across the "WARD SNDR" link in the keypad (see the
Keypad Installation
Instructions
). Assign the Node/loudspeaker to all used wards. The keypad sounder will
operate only when the output is switched on, i.e. when a sound is required for the
specified ward.
29 – Perimeter
Activates when the selected ward has a Perimeter zone (page 25) in alarm; deactivates
when the alarm is reset.
30 – Shunted
Activates when the selected ward has one or more zone shunted (by User option 1-3);
deactivates when the zones are reinstated.
31 – AlwaysOff
Never activates.
32 – SetStrobe
Activates when there is an alarm in the selected ward, and deactivates when a user resets
the alarm. The control panel also activates this output for 10 seconds after a user sets the
ward.
33 – Access
If the Access Code Only configuration option is set (page 87), this output activates when a
user code of type Access assigned to the selected ward is entered. If the Access All Codes
option is set (page 87), this output activates when any valid user code assigned to the
selected ward is entered. The output deactivates one second later if the output is latched,
or for the length of the pulse if the output is pulsed.
34 – LS Open
Active when a Lock Set zone (page 25) in the selected ward is unlocked.
35 – PSU Batt
Activates while a PSU Battery zone (page 26) in the selected ward is active.